- Insulation resistance measurement:
- test voltage: 50, 100, 250, 500, 1000 V,
- continuous indication of insulation resistance or leakage current,
- automatic discharge of capacitance of tested object after the insulation resistance measurement,
- acoustic signalling of five-second periods to facilitate obtaining time characteristics,
- indication of actual test voltage during the measurement,
- protection against measuring live objects,
- three-lead measurement.
- Continuity measurement of protective and equipotential conductors according to EN 61557 - 4 with the >200 mA current
- Low-voltage circuit continuity and resistance measurement:
- circuit resistance measurement (<1999 ) with the <15 mA current,
- quick sound signal if circuit resistance is below 30Ω.
- Capacitance measurement during the R ISO measurement
- Measurement of alternating and direct voltages in the 0...600 V range.
- Power supply: 4 AA disposable or rechargeable batteries, monitoring of power supply voltage.
- Meter conform to EN 61557.
Electric safety:
- type of insulation: double, according to EN 61010 - 1 and IEC 61557
- measurement category: IV 600 V (III 1000 V) according to EN 61010 - 1
- protection class acc. to EN 60529: IP67
Other technical specifications:
- power suply: 4 alkaline batteries or or battery package Ni-MH
- weight: ~1 kg
- dimentions: 220 x 100 x 60 mm
Insulation resistance measurement
Measuring range according to EN 61557 - 2 for U N =50 V : 50 kΩ...250,0 MΩ
Range | Resolution | Accuracy |
0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) |
1,000...9,999 MΩ | 0,001 MΩ | |
10,0...99,99 MΩ | 0,01 MΩ | |
100,0...250,0 MΩ | 0,1 MΩ |
Measuring range according to EN 61557 - 2 for U N =100 V : 100 kΩ...500,0 MΩ
Range | Resolution | Accuracy |
0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) |
1, 000...9,999 MΩ | 0,001 MΩ | |
10,0...99,99 MΩ | 0,01 MΩ | |
100,0...500,0 MΩ | 0,1 MΩ |
Measuring range according to EN 61557 - 2 for U N =250 V : 250 kΩ...2,000 GΩ
Range | Resolution | Accuracy |
0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) |
1,000...9,999 MΩ |
0,001 MΩ | |
10,0...99,99 MΩ |
0,01 MΩ | |
100,0...999,0 MΩ | 0,1 MΩ | |
1,000...2,000 GΩ | 0,001 GΩ |
Measuring range according to PN-EN 61557 - 2 for U N =500 V : 500 kΩ...5,00 GΩ
Range | Resolution | Accuracy |
0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) |
1,000...9,999 MΩ | 0,001 MΩ | |
10,00...99,99 MΩ | 0,01 MΩ | |
100,0...999,0 MΩ | 0,1 MΩ | |
1,000...5,000 GΩ | 0,001 GΩ | ±(4% m.v. + 6 digits) |
Measuring range according to EN 61557 - 2 for U N =1000 V : 1000 kΩ...10,00 GΩ
Range | Resolution | Accuracy |
0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) |
1,000...9,999 MΩ | 0,001 MΩ | |
10,00...99,99 MΩ | 0,01 MΩ | |
100,0...999,0 MΩ | 0,1 MΩ | |
1,000...5,000 GΩ | 0,001 GΩ | ±(4% m.v. + 6 digits) |
5,00...10,00 GΩ | 0,01 GΩ |
Continuity measurement of protective and equipotential conductors with the 200 mA current
Measuring range according to EN 61557 - 4: 0,10...1999 Ω
Range | Resolution | Accuracy |
0,00...19,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
20,0...199,9 Ω | 0,1 Ω | |
200...1999 Ω | 1 Ω |
±(4% m.v. + 3 digits) |
- Voltage on open terminals: <8 V
- Output current at R <2 Ω: I SC >200 mA: I SC >200 mA
- Compensation of test leads’ resistance
- Unidirectional current flow
Low-voltage and resistance measurement
Range | Resolution | Accuracy |
0,0...199,9 Ω | 0,1 Ω | ±(3% m.v. + 3 digits) |
200...1999 Ω | 1 Ω |
- Voltage on open terminals: <8 V
- Current for closed terminals 5 mA < ISC < 15 mA
- Sound signal and green LED on when measured resistance < 30 Ω ± 50%
- Compensation of test leads’ resistance,
Capacitance measurements
Range | Resolution | Accuracy |
1...999 nF | 1 nF | ±(5% m.v. + 5 digits) |
1,00...9,99µF | 0,01µF |
- Capacitance value displayed during the R ISO measurement
- For test voltages below 100 V and measured resistance below 10 MΩ, unspecified capacitance measurement error
Measurement of alternating and direct voltage
Range | Resolution | Accuracy |
0,0...299,9 V | 0,1 V | ±(2% m.v. + 6 digits) |
300...600 V | 1 V | ±(2% m.v. + 2 digits) |
- Frequency range: 45...65 Hz