MRU-200-GPS is the only meter in the market which uses all measurement methods.

Possible measurements:
  • earth resistance measurment with 2-pole, 3-pole,4-pole method,
  • impulse earth impedance measurement, three kinds of measuring impulse 4/10μs, 8/20μs, 10/350μs,
  • earth resistance measurement without disconnecting measured earths (using clamp),
  • two clamps earth resistance measurement without auxiliary test probs,
  • earth resistivity measurement,
  • continuity measurement,
  • leakage current measurement.
  • built in GPS,
  • GPS coordinates of the measurement are stored in meter memory.

Earth resistance measurement - fall of potential method with clamps



It allows to take the measurements of:

  • earth resistance using auxiliary electrodes,
  • earth resistance using auxiliary electrodes and clamp (for measurements of multiple earthing)
  • earth resistance using double clamps (for measurement of earthing when it is impossible to use auxiliary electrodes),
  • impulse earth impedance (without disconnecting measured earthing),
  • ground resistivity (Wenner method),
  • current using the clamp (e.g. leakage) and flexible clamp (Rogowsky coil),
  • measurement of continuity of equipotential bondings and protective conductors (meeting the requirements of IEC 60364 - 6 - 61:2000 section 6.12.2) with auto-zero function – with current 200 mA.

Additionally:

  • measurement of resistance of auxiliary electrodes R S and R H ,
  • measurement of interference voltage,
  • measurement of interference frequency,
  • measurement in the presence of interference voltage in the power network
    with frequency 16 2/3 Hz, 50 Hz, 60 Hz and 400 Hz (with automatic selection of proper frequency of measuring signal or with manual selection),
  • selection of maximum measuring voltage (25 V and 50 V)
  • introducing the distance between the electrodes for the resistivity in metres (m) and feet (ft),
  • memory of 990 measurements (10 banks of 99 cells each),
  • calibration of clamp used,
  • real time clock (RTC),
  • data transmission to the computer (USB),
  • indication of battery state.

Electric security:

  • type of insulation: double, according to EN 61010 - 1 and IEC 61557
  • measurement category: CAT IV 300 V acc. to EN 61010 - 1
  • protection class acc. to EN 60529: IP54

Rated operational conditions:

  • operation temperature: -10...+50°C
  • storage temperature: -20...+70°C
  • humidity: 20...80%

Other technical data:

  • LCD display: graphic, backlighted
  • interface: USB
  • number of measurements carried out of set of batteries: > 1200
  • warranty: 24 months

Measurement of interference voltage

Range Resolution Accuracy
0...100 V 1 V ±(2% m.v. + 3 digits)

Measurement of interference frequency

Range Resolution Accuracy
15...450 Hz 1 Hz ±(1% m.v. + 2 digits)

Measurement of earthing resistance (method 3- and 4-pole)
measurement range to IEC61557 - 5: 0,100 Ω...19,9 kΩ

Range Resolution Accuracy
0,000...3,999 Ω 0,001 Ω ±(2% m.v. + 4 digits)
4,00...39,99 Ω 0,01 Ω ±(2% m.v. + 2 digits)
40,0...399,9 Ω 0,1 Ω
400...3999 Ω 0,001 kΩ
4,00k...19,99 kΩ 0,01 kΩ ±(5% m.v. + 2 digits)

Measurement of continuity of equipotential bondings and protective conductors (R cont )
measurement range to IEC61557 - 4: 0,045 Ω...19,99 kΩ

Range Resolution Accuracy
0,000...3,999 Ω 0,001 Ω ±(2% m.v. + 4 digits)
4,00...39,99 Ω 0,01 Ω ±(2% m.v. + 2 digits)
40,0...399,9 Ω

0,1 Ω

400...3999 Ω 0,001 kΩ
4,00k...19,99 kΩ 0,01 kΩ ±(5% m.v. + 2 digits)

Measurement of resistance of auxiliary electrodes R H and R S

Range Range Accuracy
0...999 Ω 1 Ω ±(5% (R S +R E +R H ) + 8 digits)
1,00k...9,99 kΩ 0,01 kΩ
10,0k...19,9 kΩ 0,1 kΩ

Measurement of multiple earthing resistance with using the clamp and auxiliary
electrodes (3p + clamp)

Range Resolution Accuracy
0,000...3,999 Ω* 0,01 Ω ±(8% m.v. + 4 digits)
10,0...99,9 Ω 0,01 Ω ±(8% m.v. + 3 digits)
100...999 Ω 0,1 Ω
1,00k...1,99 kΩ 1 Ω

* - in range 0,000…0,045 Ω the accuracy is not specified.

Measurement of multiple earthing resistance with using double clamps

Range Resolution Accuracy
0,00...19,99 Ω 0,1 Ω ±(10% m.v. + 3 digits)
20,0...149,9 Ω 0,1 Ω ±(20% m.v. + 3 digits)

Measurement of ground resistivity Measurement method: Wennera, ρ=2πLR E

Range Resolution Accuracy
0,0...199,9 Ωm 0,1 Ωm depending on measurement
accuracy RE with 4p method,
but not less than ±1 digit
200...1999 Ωm 1 Ωm
2,00k...19,99 kΩm 0,01 kΩm
20,0k...99,9 kΩm 0,1 kΩm
100k...999 kΩm 1 kΩm

L – distance between probes: 1...50 m
 

Measurement of AC current (leakage)

Range Resolution Accuracy
0,1...99,9 mA 1 0,1 mA ±(8% m.v. + 5 digits)
100...999 mA 1 1 mA ±(8% m.v. + 3 digits)
1,00...4,99 A 1,2 0,01 A ±(5% m.v. + 5 digits) 1
unspecified 2
5,00...9,99 A 1,2 0,01 A ±(5% m.v. + 5 digits)
10,0...99,9 A 1,2 0,1 A
100...300 A 1,2 1 A

1 – receiving clamp (diameter 52 mm) – C-3
2 – flexible clamp (Rogowsky coil) with diameter 400 mm – F-1

Measurement of dynamic earthing resistance (R D ) with impulse wave method (4p )

Range Resolution Accuracy
0,0...99,9 Ω 0,1 Ω ±(2,5% m.v. + 3 digits)
100...199 Ω 1 Ω

choice impulse edges: 4/10μs, 8/20μs, 10/350μs

„m.v.”- measured value

Complete device information
Manufacturer site:

Link

Write a review

Please login or register to review

Sonel MRU-200-GPS Earth Resistance and Resistivity Meter

  • Brand: Sonel S.A.
  • Model: MRU-200-GPS
  • Product Number: WMGBMRU200GPS
  • Availability: 2 to 14 days order processing
  • 0.00€


Tags: Sonel MRU-200-GPS Earth Resistance and Resistivity Meter