MPI-530-IT meter is a multi-functional instrument for electric shock protection measurements including the option of various methods for measuring earthing and earthing resistance. Sonel MPI-530-IT allows testing of residual current devices (RCD), types AC, A, F and B also in IT network. Additionally the meter enables its user to analyse power supply parameters, records and displays them on its screen. The instrument automatically measures the insulation resistance in a socket and in 3 -, 4 - and 5-wire cables when used with AutoISO-1000C adapter. Measurement results may be continuously verified, depending on user’s demand or according to binding regulations. Memory of the instrument may store tens of thousands of measurements allowing users to store them in a structure of a protocol and describe individual measurement points.

Measurement of short circuit loop impedance Z L-PE , Z L-N , Z L-L 
Test current: 23/40 A; measuring range acc. to IEC 61557: 0,13...1999,9 Ω 
(for 1.2 m test lead):

Display range Resolution Accuracy
0,000...19,999 Ω 0,001 Ω ±(5% m.v. + 0,03 Ω)
20,00...199,99 Ω 0,01 Ω ±(5% m.v. +0,3 Ω)
200,0...1999,9 Ω 0,1 Ω ±(5% m.v. + 3 Ω)
  • Rated voltage: 95...270 V (for Z L-PE and Z L-N ) and 95...440 V (for Z L-L )
  • Frequency: 45...65 Hz;

Measurement of short circuit loop impedance Z L-PE in RCD mode 
Test current: 15 mA, measuring range acc. to IEC 61557: 0,50...1999 Ω

Display range Resolution Accuracy
0,00...19,99 Ω 0,01 Ω ±(6% w.m. + 10 digits)
20,0...199,9 Ω 0,1 Ω ±(6% w.m. + 5 digits)
200...1999 Ω 1 Ω
  • Rated voltage: 95...270 V
  • Frequency: 45...65 Hz

Measurement of earth resistance RE with the 3p and 4p method 
Measuring range acc. to IEC 61557 - 5:

  • 0,50 Ω…1,99 kΩ for test voltage 50 V
  • 0,56 Ω…1,99 kΩ for test voltage 25 V
Display range Resolution Accuracy
0,00...9,99 Ω 0,01 Ω ±(2% m.v. + 4 digits)
10,0...99,9 Ω 0,1 Ω ±(2% m.v.. + 3 digits)
100...999 Ω 1 Ω
1,00...1,99 kΩ 0,01 kΩ
  • test voltage: 25 V or 50 V rms
  • test current: 20 mA, sinusoidal rms 125 Hz (for f n =50 Hz) and 150 Hz (for f n =60 Hz)
  • measurement blocked at interference voltage U N > 24 V
  • maximum measured interference voltage U nmax = 100 V
  • maximum resistance of auxiliary earth electrodes 50 kΩ 
     

Selective earth resistance measurement with clamp (3p + clamp)

Display range Resolution Accuracy
0,00...9,99 Ω 0,01 Ω ±(8% m.v. + 4 digits)
10,0...99,9 Ω 0,1 Ω
100...999 Ω 1 Ω
1,00...1,99 kΩ 0,01 kΩ
  • measurement with additional current clamp
  • interference current measuring range: up to 9,99 A

Selective earth measurement with two clamps

Display range Resolution Accuracy
0,00...9,99 Ω 0,01 Ω ±(10% m.v. + 4 digits)
10,0...99,9 Ω 0,1 Ω
100...999 Ω ±(20% m.v. + 4 digits)
  • measurement with transmitting and receiving clamps
  • interference current measuring range: up to 9,99 A

Soil resistivity mesurement (ρ)

Display range Resolution Accuracy
0,0...99,9 Ωm 0,1 Ωm Depending on accuracy
of R E measurement
100...999 Ωm 1 Ωm
1,00...9,99 Ωm 0,01 kΩm
10,0...99,9 kΩm 0,1 kΩm
  • measurement with Wenner’s method
  • distance settable in metres or feet
  • distance range: 1...30 m (1...90 feet)

Phase sequence indication

  • Phase sequence indication: conforming, non-conforming
  • Mains voltage range UL-L: 100...440 V (45...65 Hz)
  • Display of phase-to-phase voltage values

Measurements of RCD parameters (voltage range 95...270 V):

RCD tripping test and measurement of tripping time tA (for t A measurement function)

RCD type Current Range Resolution Accuracy
General and
short-time
delay
0,5*I Δn 0...300 ms

1 ms

± (2% m.v. + 2 digits)

(for RCD with I Δn =10 mA
and 0,5xI Δn uncertainty:
±(2% m.v. + 3 digits)

1*I Δn
2*I Δn 0...150 ms
5*I Δn 0...40 ms
Selective 0,5*I Δn 0...500 ms
1*I Δn
2*I Δn 0...200 ms
5*I Δn 0...150 ms
  • accuracy of residual current application: for 0,5*I Δn :-8...0% for 1*I Δn , 2*I Δn , 5*I Δn : 0...8%

Measurement of RCD tripping current IA for sinusoidal residual current (AC type)

Rated
current
Meas. range Resolution Test current Accuracy
10 mA 3,3...10,0 mA 0,1 mA 0,3 x I Δ ..1,0 x I Δ ± 5%I Δn
30 mA 9,0...30,0 mA
100 mA 33...100 mA 1 mA
300 mA 90...300 mA
500 mA 150...500 mA
1000 mA 330...1000 mA
  • The measurement can be started from positive or negative half-period of forced leakage current

Measurement of RCD tripping current IA for unidirectional residual current and unidirectional 
with the 6 mA DC bias (type A)

Rated
current
Meas. range Resolution Test current Accuracy
10 mA 3,5...20,0 mA 0,1 mA 0,35 x I Δn ..2,0 x I Δn ±10%I Δn
30 mA 10,5...42,0 mA 0,35 x I Δn ..1,4 x I Δn
100 mA 35,0...140 mA 1 mA
300 mA 105...420 mA
500 mA 175...700 mA

Measurement for positive or negative half-periods of forced leakage current

Measurement of RCD tripping current IA for direct residual current (type B)

Rated
current
Meas. range Resolution Test current Accuracy
10 mA 2,0...20,0 mA 0,1 mA 0,4 x I Δn ..2,0 x I Δn ±10%I Δn
30 mA 6...60 mA 1 mA
100 mA 20...200 mA
300 mA 60...600 mA
500 mA 100...1000 mA
  • Measurement for positive or negative half-periods of forced leakage current
  • I Δn - rated residual current

Insulation resistance measurements 
Measuring range acc. to IEC 61557 - 2:

  • for U N = 50 V: 50 kΩ...250 MΩ
  • for U N = 100 V: 100 kΩ...500 MΩ
  • for U N = 250 V: 250 kΩ...999 MΩ
  • for U N = 500 V: 500 kΩ...2 GΩ
  • for U N = 1000 V: 1,000 MΩ...9,99 GΩ
Display range*) Resolution Accuracy
0...1999 kΩ 1 kΩ ±(3% m.v. + 8 digits)
2,00...19,99 MΩ 0,01 MΩ
20,0...199,9 MΩ 0,1 MΩ
200...999 MΩ 1 MΩ
1,00...9,99 MΩ 0,01 GΩ ±(4% m.v. + 6 digits)
  • *) not greater than measuring range for given voltage

Low-voltage measurement of resistance and circuit continuity 
Measurement of protective conductor continuity with the ±200 mA current

Range Resolution Accuracy
0,00...19,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
20,0...199,9 Ω 0,1 Ω
200...400 Ω 1 Ω
  • voltage on open terminals: 4…9 V
  • output current at R < 2 Ω: min. 200 mA
  • autocalibration of test leads
  • measurements for both current polarities

Illuminance measurement

Range Resolution Accuracy
0,1...99,9 lx 0,1 lx ±(5% m.v. + 2 digits)
100...999 lx 1 lx
1,00...9,99 klx 0,01 lx
10,0...19,9 klx 0,1 lx
  • measurement in luxes (lx) or feet-candles (fc)

ANALYSIS AND RECORDING OF SINGLE-PHASE SYSTEM

  • Voltage measurement ULN: 0...500 V
  • Frequency range of measured voltages: 45,0...65,0 Hz
  • Frequency measurement range for 50...500 V voltages: 45,0...65,0 Hz (basic uncertainty max. ± 0,1% m.v. + 1 digit)
  • cosφ measurement: 0,00...1,00 (resolution 0,01)
  • Measurement and recording in single-phase system

Current measurement (True RMS)

Clamps Range Resolution Accuracy *
C-3, C-6 0,0...99,9 mA 0,1 mA ±(5% m.v. + 3 digits)
100...999 mA 1 mA
C-3,C-6
F-1, F-2, F-3
1,00...9,99 A 0,01 A ±(5% m.v. + 5 digits)
(C-3, C-6)
±(0,1% In + 2 digits)
(F-1, F-2, F-3)
10,0...99,9 A 0,1 A
100...999 A 1 A
F-1, F-2, F-3 1,00...3,00 kA 0,01 kA
  • * the accuracy of current clamps must also be taken into account

Measurement of active power P, reactive power Q, apparent power S and cosφ

Range
[W], [VA], [var]
Resolution
[W], [VA], [var]
Accuracy *
0...999 1 ±(7% m.v. + 3 digits)
1,00...9,99 k 0,01 k
10,0...99,9 k 0,1 k ±(7% m.v. + 5 digits)
100...999 k 1 k
1,00...1,50 M 0,01 M
  • voltage range: 0…500 V
  • current range: 0...1000 A (3000 A)
  • mains rated frequency fn: 50 Hz, 60 Hz 
     

Voltage harmonics measurement

Range Resolution Nr harm. Accuracy
0,0...500 V 0,1 (1*) V 1,2,...15 ±(5% m.v. + 3 digits)
16,...40 ±(5% m.v. + 10 digits)
  • in addition display of h02...h40 values as percent of h01 (up to 999%)
  • *) from 300 V to 500 V

THD (in relation to the 1 st harmonics)

Resolution Accuracy
THD-F voltage
(h = 2…40)
0,0…999,9%
for U RMS ≥ 1% U nom
 
0,1% ±5%
THD-F current
(h = 2...40)
0,0…999,9%
for I RMS ≥ 1% I nom
0,1% ±5%

NOTE: “m.v.” means “ measured value”

The instruments conforms to:

  • EN 61010 - 1 (general safety requirements)
  • EN 61010 - 031 (detailed safety requirements)
  • EN 61326 (electromagnetic compatibility)
  • EN 61557 - 10 (requirements for combined instruments)
  • IEC 60364 - 6-61 / HD 60364 - 6 (measurements - verification)
  • IEC 60364 - 4-41 / HD 60364 - 4-41 (measurements – protection against electric shock)
  • EN 04700 (measurements – acceptance tests)
  • EN 12464 (lighting of work places)
  • DIN VDE 0100
  • DIN VDE 0413
  • BS 7671
Complete device information
Manufacturer site: