Transmitter connections can be via 2, 3 or 4 wires. With 4-wire hookup, 2 wires are used for excitation and two separate wires are used to sense the voltage across the resistance to be measured, thereby eliminating any lead resistance effects. With 3-wire hookup, the transmitter senses the combined voltage drop across the RTD plus two excitation leads. It also senses the voltage drop across one excitation lead, and then subtracts twice this voltage from the combined total. This technique effectively subtracts the lead resistance if the excitation leads are the same.
All resistance ranges are digitally calibrated at the factory, with calibration factors stored in EEPROM on the signal conditioner board. This allows ranges and signal conditioner boards to be changed in the field without recalibrating the transmitter. If desired, the transmitter can easily be calibrated using external standards plus scale and offset in software.
High read rates at up to 60 or 50 conversions per second while integrating the signal over a full power cycle are ideal for high-throughput manufacturing processes. Peak and valley values are automatically captured and may be displayed via a front panel pushbutton command or a control signal at the rear connector, or be transmitted as serial data.
Custom curve linearization, available with the Extended version, makes this transmitter suitable for use with transducers whose output is a non-linear changing resistance. Linearization is provided by curvilinear spline fits, and the reading can be scaled in software for user-selected engineering units of measure.
Standard features of Laureate LT transmitters include:
- 4-20 mA, 0-10V or -10V to +10V analog transmitter output, isolated, jumper-selectable and user scalable. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy of a reading from -99,999 to +99,999 counts that is also transmitted digitally. Output isolation from signal and power grounds eliminates potential ground loop problems.
- Serial communications output, RS232 or RS485 (half or full duplex), jumper selectable. Three protocols are user selectable: Modbus RTU, Modbus ASCII, or Laurel ASCII. Modbus operation is fully compliant with Modbus Over Serial Line Specification V1.0 (2002). The Laurel ASCII protocol is simpler than the Modbus protocol and is recommended when all devices are Laureates.
- Dual solid state relays, isolated, for alarm or control. Rated 120 mA at 140 Vac or 180 Vdc.
- Universal 85-264 Vac power. Low-voltage 10-48 Vdc or 12-32 Vac power is optional.
Easy Transmitter programming is via Laurel's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL04).
Features
- 4-20 mA, 0-20 mA, 0-10V or -10V to +10V transmitter output, 16 bits, isolated
- RS232 or RS485 serial data output, Modbus or Laurel ASCII protocol, isolated
- Dual 120 mA solid state relays for alarm or control, isolated
- Five jumper-selectable resistance ranges of 20.000 ohm to 200.00 kohm
- Fixed factory-special resistance ranges of 2.0000 ohm or 2.0000 Mohm
- 0.1 milliohm resolution on 2 ohm scale for contact resistance measurements
- Custom curve linearization for changing resistance transducers
- 2, 3 or 4-wire connection with lead resistance compensation
- Analog output resolution 0.0015% of span (16 bits), accuracy ±0.02% of span
- DIN rail mount housing only 22.5 mm wide, detachable screw-clamp connectors
- Universal 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac power
Specifications
Range | Resolution | Accuracy | Excitation Current *** |
---|---|---|---|
0-2.0000 Ω | 0.1 mΩ | ±0.01% of reading ± 2 counts |
5 mA |
0-20.000 Ω | 1 mΩ | 5 mA | |
0-200.00 Ω | 10 mΩ | 500 µA | |
0-2000.0 Ω | 100 mΩ | 50 µA | |
0-20000 Ω | 1 Ω | 5 µA | |
0-200.00 kΩ | 10 Ω | 500 nA | |
0-2.0000 MΩ | 100 Ω | 500 nA |
* | Jumper-selectable, precalibrated range. |
** | Factory-set fixed range. |
*** | The applied excitation current is sensed by the meter, which operates in a ratiometric mode and automatically compensates for any changes in excitation. |
Signal Input | |
---|---|
Input Resolution | 16 bits (65,536 steps) |
Input Accuracy | ±0.01% of reading ± 2 counts |
Update Rate, Max | 50/sec at 50 Hz, 60/sec at 60 Hz |
Analog Output (standard) | |
Output Levels | 4-20 mA, 0-20 mA, 0-10 Vdc, -10 to +10Vdc (user selectable) |
Compliance, 4-20 mA | 10V (0-500Ω load) |
Compliance, 0-10V | 2 mA (5 kΩ load or higher) |
Output Resolution | 16 bits (65,536 steps) |
Output Accuracy | 0.02% of output span plus conversion accuracy |
Output Isolation | 250V rms working, 2.3 kV rms per 1 minute test |
Serial Data Output (standard) | |
Signal Types | RS232 or RS485 (half or full duplex), jumper selectable |
Data Rates | 300, 600, 1200, 2400, 4800, 9600, 19200 baud |
Output Isolation | 250V rms working, 2.3 kV rms per 1 min test |
Serial Protocols | Modbus RTU, Modbus ASCII, Laurel ASCII |
Modbus Compliance | Modbus over Serial Line Specification V1.0 (2002) |
Ethernet Connector | RJ45 jack for 10/100 Base-T Ethernet cable |
RS232/485 Connector | Screw terminals for easy daisy chaining |
Digital Addresses | 247 for Modbus, 31 for Laurel ASCII |
Dual Relay Output (standard) | |
Relay Type | Two solid state relays, SPST, normally open, Form A |
Load Rating | 120 mA at 140 Vac or 180 Vdc |
Power Input | |
Standard Power | 85-264 Vac or 90-300 Vdc |
Low Power Option | 10-48 Vdc or 12-32 Vac |
Power Frequency | DC or 47-63 Hz |
Power Isolation | 250V rms working, 2.3 kV rms per 1 min test |
Power Consumption | 2W typical, 3W with max excitation output |
Mechanical | |
Dimensions | 129 x 104 x 22.5 mm case |
Mounting | 35 mm rail per DIN EN 50022 |
Electrical Connections | Plug-in screw-clamp connectors |
Environmental | |
Operating Temperature | 0°C to 55°C |
Storage Temperature | -40°C to 85°C |
Relative Humidity | 95% at 40°C, non-condensing |
Cooling Required | Mount transmitters with ventilation holes at top and bottom. Leave 6 mm (1/4") between transmitters, or force air with a fan. |
Pinout
Resistance Measurement with Excitation & Lead Compensation
Ohm transmitter hookup can be via 2, 3 or 4 wires to the J5 connector. The transmitter applies a fixed excitation current for each resistance range. | |
In 4-wire hookup, different pairs of leads are used to apply the excitation current and sense the voltage drop across the unknown resistance, so that the IR drop across the excitation leads is not a factor. | |
In 3-wire hookup, the transmitter senses the combined voltage drop across the unknown resistance plus two excitation leads. It also senses the voltage drop across one excitation lead, and then subtracts twice this voltage from the combined total. This technique effectively subtracts all lead resistance and compensates for ambient temperature changes if the two excitation leads are identical. | |
In 2-wire hookup, the transmitter senses the combined voltage drop across the unknown resistance and both lead wires. The voltage drop across the lead wires can be measured by shorting out the resistance during transmitter setup, and this voltage is then automatically subtracted from the combined total. However, changing resistance of the lead wires due to ambient temperature changes will not be compensated. |
Applications
QA Application with Relays in Passband Mode
A deviation limit (50 mΩ in this example) is set up around both sides of a setpoint. The relay closes (or opens) when the reading falls within the deviation band, and opens (or closes) when the reading falls outside of this band. This mode sets up a passband around the setpoint and can be used for contact resistance testing in a production environment. |
Datasheet, Manual, Mechanical and Serial I/O info. | |